Single-phase On-grid Solar Inverter
BD30KTR-MT | BD50KTR-MT | BD100KTR-MT | BD150KTR-MT | BD250KTR-MT | BD500KTR-MT | |
AC (On-grid) | ||||||
Max. Output Power | 33kVA | 55kVA | 110kVA | 165kVA | 275kVA | 550kVA |
Rated power | 30kW | 50kW | 100kW | 150kW | 250kW | 500kW |
Rated Current | 43A | 72A | 144A | 216A | 361A | 722A |
Max. Output Current | 48A | 80A | 159A | 238A | 397A | 794A |
Rated Voltage | 400V, 3W + N + PE | |||||
Operating Voltage Range | 320V ~ 460V | |||||
Rated Frequency | 50Hz / 60Hz | |||||
Power Factor | 1 leading ~ 1 lagging | |||||
THDi | <3% | |||||
AC (Off-grid) | ||||||
Rated Voltage | 400V | |||||
Rated Frequency | 50Hz / 60Hz | |||||
Overload Capability | 110% (continous) | |||||
THDu | < 1% linear; < 5% nonlinear | |||||
DC (Battery) | ||||||
Battery Voltage Range | 250V ~ 850V | 320V ~ 850V | 420V ~ 850V | 420V ~ 850V | 420V ~ 850V | 500V ~ 850V |
Max.Current | 137A | 178A | 270A | 405A | 673A | 1128A |
Efficiency | ||||||
Max. Efficiency | 96.30% | 96.50% | 97.10% | 97.10% | 97.30% | 97.50% |
Communication | ||||||
Display | LCD | |||||
BMS Communication | RS485, CAN | |||||
EMS Communication | RS485, TCP/IP | |||||
Standard Compliance | ||||||
Certificates | CE, TÜV, CGC | |||||
General Data | ||||||
Dimensions (W x H x D) | 800 × 2050 x 800 mm | 1200 × 2050 x 800 mm | 1600 × 2050 x 1050 mm | |||
Weight | 605kg | 676kg | 936kg | 1057kg | 1582kg | 2665kg |
Operation Temperature | -30°C ~ +55°C | |||||
Cooling Method | Smart Air Cooling | |||||
Protection Degree | IP21 | |||||
Noise Emission | <75dB | |||||
Max. Operating Altitude | 5000m (derating above 3000m) | |||||
Relative Humidity | 0 ~ 95% (non-condensing) | |||||
Transformer Ratio | 100 / 400 | 200 / 400 | 270 / 400 | 270 / 400 | 270 / 400 | 315 / 400 |
Power Consumption | < 10W | |||||
On/Off Grid Transfer | Automatic |